EKL medium/premium ECT connection technology
Product Description | EKL medium/premium ECT connection technology |
Product Type | 27-5A3.-…. |
Brand | Bartec |
- Simple and fast installation
- Low stock levels needed (because it can be used as terminal or connection)
- High chemical resistance, for almost all industrial chemicals and solvents
Description
The EKL Connection Technology is a connection system for EKL medium and EKL premium for use in potentially explosive atmospheres. Depending on the design, the ECT connection technology may be used to connect a cold lead or to connect two heating cables. Butt connectors, which ensure a reliable and permanent connection, are used for the electrical connection of the heating wire and the protective braid. Using pre-assembled cold leads and our connection technology, complete heating circuits can be constructed quickly and flexibly.
Technical Data
Protection Class | IP 66 (EN/IEC 60079-0) |
Dimentions | ECT35: 176 mm/35 mm ECT45: 212 mm/45 mm |
Voltage | max. 750 V |
Current | 32 A – 129 A |
Connection | External diameter conductor: 3,2 mm² – 12,4 mm² |
Ambient temperature | -60 °C to +200 °C |
Explosion Protection
Marking | Ex II 2G Ex eb IIC Gb Ex II 2D Ex tb IIIC Db |
Certification | BVS 16 ATEX E 018 U IECEx BVS 16.0014U |
- General Info
-
Description
The EKL Connection Technology is a connection system for EKL medium and EKL premium for use in potentially explosive atmospheres. Depending on the design, the ECT connection technology may be used to connect a cold lead or to connect two heating cables. Butt connectors, which ensure a reliable and permanent connection, are used for the electrical connection of the heating wire and the protective braid. Using pre-assembled cold leads and our connection technology, complete heating circuits can be constructed quickly and flexibly.
- Technical Data
-
Technical Data
Protection Class IP 66 (EN/IEC 60079-0) Dimentions ECT35: 176 mm/35 mm
ECT45: 212 mm/45 mmVoltage max. 750 V Current 32 A – 129 A Connection External diameter conductor: 3,2 mm² – 12,4 mm² Ambient temperature -60 °C to +200 °C - Explosion Protection
-
Explosion Protection
Marking Ex II 2G Ex eb IIC Gb
Ex II 2D Ex tb IIIC DbCertification BVS 16 ATEX E 018 U