HTSB system – Cold applied technology and brass cable gland

null
Product Description HTSB system – Cold applied technology and brass cable gland
Product Type 05-009.-0…
Brand Bartec
  • Direct entry of a heating tape into the junction box
  • Connection and termination in one set
  • Space-saving and economic solution
  • Easy design and assembling with silicone cold-applied technology

Description

The heating tape is connected directly in the junction box, the two supply conductors of the self-limiting heating tape HTSB (Type no. 07-5809-2..N) are insulated with silicone glue and a silicone hose. A green/yellow protective tube is pulled over the braiding.
The end of the self-limiting heating tape is insulated with silicone glue and an end cap.

Technical Data

Power see HTSB data: 15, 30, 45, 60, 75, 90 W/m
Ambient temperature Cold applied technology: -55 °C to +200 °C
Cable gland: -55 °C to +180 °C

Explosion Protection

Marking Ex II 2G Ex e IIC T2, T3 Gb
Ex II 2D Ex tb IIIC T200 °C, T195 °C Db
Datasheet
General Info

Description

The heating tape is connected directly in the junction box, the two supply conductors of the self-limiting heating tape HTSB (Type no. 07-5809-2..N) are insulated with silicone glue and a silicone hose. A green/yellow protective tube is pulled over the braiding.
The end of the self-limiting heating tape is insulated with silicone glue and an end cap.

Technical Data

Technical Data

Power see HTSB data: 15, 30, 45, 60, 75, 90 W/m
Ambient temperature Cold applied technology: -55 °C to +200 °C
Cable gland: -55 °C to +180 °C
Explosion Protection

Explosion Protection

Marking Ex II 2G Ex e IIC T2, T3 Gb
Ex II 2D Ex tb IIIC T200 °C, T195 °C Db