EKL Light Flexible Single-core Heating Cable
Product Description | EKL Light Flexible Single-core Heating Cable |
Product Type | 27-582.-5A6A… |
Brand | Bartec |
- Constant power output per meter
- Steam purging resistant, suitable for high temperatures up to +260 °C
- Easy installation, very flexible
- Highly resistant to almost all industrial chemicals and solvents
Description
EKL light is a serial resistant heating cable for use in industrial and commercial areas. It is suitable for frost protection applications and temperature maintenance on pipes and tanks and it is also extremely flexible.
This makes EKL light easy to install, even on irregular shapes such as on pumps, valves and flanges. The PFA protective jacket gives the EKL light a high degree of chemical and mechanical resistance, even at high temperatures.
In economical terms, EKL light is a genuine alternative to SLHBs when the latter’s maximum heating circuit lengths are exceeded.
With pre-assembled cold leads and our connection technology, complete heating circuits can be set up quickly and flexibly.
Technical Data
Dimensions | Diameter: see data sheet Bending radius: min. 5 x external diameter Minimum installation spacing: 20 mm |
Heat output | max. 25 W/m |
Voltage | 500 V |
Current | 32 – 129 A (see data sheet) |
Resistance | Value from 0.8 Ω/km to 8000 Ω/km (see data sheet) Protective braid: < 18.2 Ω/km Resistance tolerance: -5 % / +10 % |
Guidelines/Norms | Electrical safety EN 62395-1 |
Ambient temperature | -60 °C to +260 °C Minimum installation temperature: -60 °C |
- General Info
-
Description
EKL light is a serial resistant heating cable for use in industrial and commercial areas. It is suitable for frost protection applications and temperature maintenance on pipes and tanks and it is also extremely flexible.
This makes EKL light easy to install, even on irregular shapes such as on pumps, valves and flanges. The PFA protective jacket gives the EKL light a high degree of chemical and mechanical resistance, even at high temperatures.
In economical terms, EKL light is a genuine alternative to SLHBs when the latter’s maximum heating circuit lengths are exceeded.
With pre-assembled cold leads and our connection technology, complete heating circuits can be set up quickly and flexibly. - Technical Data
-
Technical Data
Dimensions Diameter: see data sheet
Bending radius: min. 5 x external diameter
Minimum installation spacing: 20 mmHeat output max. 25 W/m Voltage 500 V Current 32 – 129 A (see data sheet) Resistance Value from 0.8 Ω/km to 8000 Ω/km (see data sheet)
Protective braid: < 18.2 Ω/km
Resistance tolerance: -5 % / +10 %Guidelines/Norms Electrical safety
EN 62395-1Ambient temperature -60 °C to +260 °C
Minimum installation temperature: -60 °C - Download