SEH Heating cable with PFA insulation M

null
Product Description SEH Heating cable with PFA insulation M
Product Type 07-5721-..3.
Brand Bartec
  • Constant power output in W/m
  • High dielectric strength up to 5 kV operation voltage
  • Highly chemical resistant PFA outer insulation jacket
  • Temperature resistant up to +260 °C
  • Nominal production length of spool 600 m
  • Rugged against abrasion

Description

Typically long line pipe work and heating elements are located in areas where access is limited. Since SEH system heating cables are installed into a carbon steel heat pipe the electrical safety against direct contact and the mechanical strength is no issue.
BARTERC solutions for SEH system heating cables offers the electrically insulated and highly temperature resistant conductor in the needed quality and with respect to the economic needs. The BARTEC engineers design the SEH system heating circuit by variation of operation voltage, cross section, maximum operation temperature and heat tube size.
The SEH heating system element generates heat used for the power output by the inductive interaction through current flow in the conductor installed in the heat pipe.

Technical Data

Dimensions Max. unspliced length: 600 m in production
Cross section: 16 mm² – 50 mm²
Weight 270 kg/km – 690 kg/km
Voltage AC 2000 V or AC 5000 V
Resistance 0.34 Ohm/km – 1.05 Ohm/km at 20 °C
Ambient temperature Maximum operation temperature -60 °C to +260 °C
Datasheet
General Info

Description

Typically long line pipe work and heating elements are located in areas where access is limited. Since SEH system heating cables are installed into a carbon steel heat pipe the electrical safety against direct contact and the mechanical strength is no issue.
BARTERC solutions for SEH system heating cables offers the electrically insulated and highly temperature resistant conductor in the needed quality and with respect to the economic needs. The BARTEC engineers design the SEH system heating circuit by variation of operation voltage, cross section, maximum operation temperature and heat tube size.
The SEH heating system element generates heat used for the power output by the inductive interaction through current flow in the conductor installed in the heat pipe.

Technical Data

Technical Data

Dimensions Max. unspliced length: 600 m in production
Cross section: 16 mm² – 50 mm²
Weight 270 kg/km – 690 kg/km
Voltage AC 2000 V or AC 5000 V
Resistance 0.34 Ohm/km – 1.05 Ohm/km at 20 °C
Ambient temperature Maximum operation temperature -60 °C to +260 °C
Download