Product Description DTW/DTB Flame-proof temperature monitor/limiter
Product Type 27-6C.2-.4112000
Brand Bartec
  • 22 A switching capacity
  • Can be used directly in Zone 1 and 2
  • Flame-proof enclosure
  • ATEX, UL, CSA, FM Approval

Description

The flameproof encapsulated temperature controllers/limiters (DTW/DTB) are designed for (trace)-heating applications in the Ex area. They can be used both for protection against frost and for maintenance temperature applications. Heating units and other operating equipment are switched on and off by means of the temperature controller when the temperature is too high or too low. The DTB temperature limiter is designed with resetting lockout; resetting (restarting) is only possible on the device. Can be used for monitoring temperature in the air or on surfaces.

Function

A change in temperature in the sensor causes a change in volume in the fluid filled in the measuring system, which in turn results in a movement of a membrane, which is connected to transmission mechanics and activates a microswitch. If the sensor temperature exceeds the pre-set level, the contact is actuated.
The temperature limiter switches off permanently if the temperature is exceeded. Once the temperature drops, the temperature limiter can be unlocked manually. If there is a break in the measuring system (leakage), the circuit remains open permanently.

Technical Data

Protection Class IP 65 / NEMA 4, 7, 9
Dimensions Capillary tube: Length: 3000 mm, Diameter: 2 mm
Bending radius: 15 mm
Sensor: Length: 203 mm, Diameter: 8 mm
Material Enclosure: Aluminium die-casting, lacquered, with internal lid seal
Capillary tube made of stainless steel
Sensor made of stainless steel
Storage temperature -40 °C up to +60 °C
Connection Terminals: Terminal screws 4/2.5 mm² (AWG 10-14)
Cable entries: 2 x M 25 borehole
Connection Terminals: Terminal screws 4/2.5 mm² (AWG 10-14)
Cable entries: 2 x M 25 borehole
Weight 1.7 kg
Voltage AC 6/ 12/ 24/ 125/ 250/ 480 Volt, 50/60 Hz
Current Switching current for controller: 22 A at AC 6/ 12/ 24/ 125/ 250/ 480 Volt
Switching current for limiter: 16 A at AC 6/ 12/ 24/ 125/ 250 Volt, 15 A at AC 480 Volt
Temperature range -4 °C up to +163 °C
Ambient temperature device: -40 °C up to +60 °C
Operating temperature range sensor: -40 °C up to +215 °C
Operating temperature range capillary tube: -50°C up to +215°C

Explosion Protection

Marking Ex II 2G Ex d IIC T6
Ex II GD Ex tb IIIC T80 °C Db
Certification LCIE 08 ATEX 6073 X
IECEx LCIE 14.0005X
Russian RTN PPC 00-38415
Russian GOST R POCC DE.ME92.B01970
Datasheet
General Info

Description

The flameproof encapsulated temperature controllers/limiters (DTW/DTB) are designed for (trace)-heating applications in the Ex area. They can be used both for protection against frost and for maintenance temperature applications. Heating units and other operating equipment are switched on and off by means of the temperature controller when the temperature is too high or too low. The DTB temperature limiter is designed with resetting lockout; resetting (restarting) is only possible on the device. Can be used for monitoring temperature in the air or on surfaces.

Function

A change in temperature in the sensor causes a change in volume in the fluid filled in the measuring system, which in turn results in a movement of a membrane, which is connected to transmission mechanics and activates a microswitch. If the sensor temperature exceeds the pre-set level, the contact is actuated.
The temperature limiter switches off permanently if the temperature is exceeded. Once the temperature drops, the temperature limiter can be unlocked manually. If there is a break in the measuring system (leakage), the circuit remains open permanently.

Technical Data

Technical Data

Protection Class IP 65 / NEMA 4, 7, 9
Dimensions Capillary tube: Length: 3000 mm, Diameter: 2 mm
Bending radius: 15 mm
Sensor: Length: 203 mm, Diameter: 8 mm
Material Enclosure: Aluminium die-casting, lacquered, with internal lid seal
Capillary tube made of stainless steel
Sensor made of stainless steel
Storage temperature -40 °C up to +60 °C
Connection Terminals: Terminal screws 4/2.5 mm² (AWG 10-14)
Cable entries: 2 x M 25 borehole
Connection Terminals: Terminal screws 4/2.5 mm² (AWG 10-14)
Cable entries: 2 x M 25 borehole
Weight 1.7 kg
Voltage AC 6/ 12/ 24/ 125/ 250/ 480 Volt, 50/60 Hz
Current Switching current for controller: 22 A at AC 6/ 12/ 24/ 125/ 250/ 480 Volt
Switching current for limiter: 16 A at AC 6/ 12/ 24/ 125/ 250 Volt, 15 A at AC 480 Volt
Temperature range -4 °C up to +163 °C
Ambient temperature device: -40 °C up to +60 °C
Operating temperature range sensor: -40 °C up to +215 °C
Operating temperature range capillary tube: -50°C up to +215°C
Explosion Protection

Explosion Protection

Marking Ex II 2G Ex d IIC T6
Ex II GD Ex tb IIIC T80 °C Db
Certification LCIE 08 ATEX 6073 X
IECEx LCIE 14.0005X
Russian RTN PPC 00-38415
Russian GOST R POCC DE.ME92.B01970
Download