Anti-condensation Motor Heater MSHex

null
Product Description Anti-condensation Motor Heater MSHex
Product Type 27-1776-. ..000..
Brand Bartec
  • Silicone-free
  • Self-limiting
  • Other length on request

Description

This flexible heating cable is used in explosive atmospheres to heat electric motors and generators at standstill. It provides reliable protection against corrosion damage and the associated mechanical breakdowns because it effectively prevents condensation from forming, even under extreme conditions.
The heater is supplied ready to connect, which is done via an M20 screwed cable connection fed into an Ex e distributor, or is directly clamped to terminals in an Ex room without a screwed connection.
As these heating cables are self-limiting, overheating is prevented, even if they are laid on top of each other. An additional temperature limiter is not required.

Structure of the heating cable

Copper power conductor wire 1.2 mm², nickel-plated
Self-limiting plastic heating element
Insulation sleeve made of FEP
Tin-plated copper braiding
Protective sleeve made of FEP

Technical Data

Dimensions Size of heating cable diameter: 10.2 mm x 4.8 mm
Bending radius: ≥ 25 mm
Heat output 12 W, 24 W, 48 W and 96 W (at 10 °C)
at a specific heating output of 45 W/m
Voltage Nominal voltage: 208 V to 254 V or 110 V to 120 V
Insulation testing: AC 1500 V for 1 minute
Connection Terminal wires with FEP isolation
fine-stranded with tin-plated copper wires 1.5 mm²,
green and yellow protective earth conductor 2.5 mm²
Ambient temperature switched on (energised) -40 °C up to +120 °C
switched off -40 °C up to +170 °C

Explosion Protection

Marking Ex II 2G Ex e IIC 200 °C (T2), T3 Gb
Certification KEMA 08ATEX0109
IECEx KEM 09.0082
IEE 11.0276
Datasheet
Operating Instructions
General Info

Description

This flexible heating cable is used in explosive atmospheres to heat electric motors and generators at standstill. It provides reliable protection against corrosion damage and the associated mechanical breakdowns because it effectively prevents condensation from forming, even under extreme conditions.
The heater is supplied ready to connect, which is done via an M20 screwed cable connection fed into an Ex e distributor, or is directly clamped to terminals in an Ex room without a screwed connection.
As these heating cables are self-limiting, overheating is prevented, even if they are laid on top of each other. An additional temperature limiter is not required.

Structure of the heating cable

Copper power conductor wire 1.2 mm², nickel-plated
Self-limiting plastic heating element
Insulation sleeve made of FEP
Tin-plated copper braiding
Protective sleeve made of FEP

Technical Data

Technical Data

Dimensions Size of heating cable diameter: 10.2 mm x 4.8 mm
Bending radius: ≥ 25 mm
Heat output 12 W, 24 W, 48 W and 96 W (at 10 °C)
at a specific heating output of 45 W/m
Voltage Nominal voltage: 208 V to 254 V or 110 V to 120 V
Insulation testing: AC 1500 V for 1 minute
Connection Terminal wires with FEP isolation
fine-stranded with tin-plated copper wires 1.5 mm²,
green and yellow protective earth conductor 2.5 mm²
Ambient temperature switched on (energised) -40 °C up to +120 °C
switched off -40 °C up to +170 °C
Explosion Protection

Explosion Protection

Marking Ex II 2G Ex e IIC 200 °C (T2), T3 Gb
Certification KEMA 08ATEX0109
IECEx KEM 09.0082
IEE 11.0276
Download
Datasheet
Operating Instructions