PLEXO TCS the plug-in connection system for PSBL, PSB, MSB and HSB systems
Product Description | PLEXO TCS the plug-in connection system for PSBL, PSB, MSB and HSB systems |
Product Type | 27-59P.-.0100001 |
Brand | Bartec |
- Cross-section of connection terminals up to 4 mm²
- Integrated strain relief: high electrical and mechanical safety
- Quick and easy installation with standard tools
- System approval in conformance to IEC/EN 60079, utilisation in the hazardous area
Description
The PLEXO TCS connection system can be used for BARTEC self-limiting heating tapes. The PLEXO TCS may be used both as an autonomous system with the heating tape or as part of the PSBL, PSB, MSB and HSB system. This modular connection technology enables the simple and reliable assembly of supply connections, splicing and remote-end terminations. PLEXO TCS is plugged and built up with a patented sealing and clamping technology.
Maintenance work and later modifications on the heating circuit can be performed quickly and flexibly. The strands from the heating tape or the supply cable are fixed in place securely using the spring-loaded terminals in the internal clamping technology
Technical Data
Protection Class | EN 60079-0: IP 65 EN 60529: IP 66/IP 68 |
Voltage | Rated voltage: max. 254 V |
Current | Rated current: PSBL: max. 16 A PSB/MSB/HSB: max. 32 A |
Connection | Rated cross-section of supply cable: max. 4 mm² |
Ambient temperature | Ex version: -60 °C to +160 °C Non Ex version: -60 °C to +160 °C Minimum installation temperature: -55 °C |
Explosion Protection
Marking | PSBL: Ex II 2G Ex eb IIC T5 Gb Ex II 2D Ex tb IIIC T95 °C Db PSB: Ex II 2G Ex eb IIC T5, T6 Gb Ex II 2D Ex tb IIIC T95 °C, T80 °C Db MSB: Ex II 2G Ex eb IIC 150 °C (T3), T4 Gb Ex II 2D Ex tb IIIC T150 °C, T130 °C Db HSB: Ex II 2G Ex eb IIC 180 °C (T3), T4 Gb Ex II 2D Ex tb IIIC T180 °C, T130 °C Db |
Certification | BVS 13 ATEX E 040 IECEx BVS 13.0048X TC RU C-DE.GB06.B.00230 |
- General Info
-
Description
The PLEXO TCS connection system can be used for BARTEC self-limiting heating tapes. The PLEXO TCS may be used both as an autonomous system with the heating tape or as part of the PSBL, PSB, MSB and HSB system. This modular connection technology enables the simple and reliable assembly of supply connections, splicing and remote-end terminations. PLEXO TCS is plugged and built up with a patented sealing and clamping technology.
Maintenance work and later modifications on the heating circuit can be performed quickly and flexibly. The strands from the heating tape or the supply cable are fixed in place securely using the spring-loaded terminals in the internal clamping technology - Technical Data
-
Technical Data
Protection Class EN 60079-0: IP 65
EN 60529: IP 66/IP 68Voltage Rated voltage: max. 254 V Current Rated current:
PSBL: max. 16 A
PSB/MSB/HSB: max. 32 AConnection Rated cross-section of supply cable: max. 4 mm² Ambient temperature Ex version: -60 °C to +160 °C
Non Ex version: -60 °C to +160 °C
Minimum installation temperature: -55 °C - Explosion Protection
-
Explosion Protection
Marking PSBL:
Ex II 2G Ex eb IIC T5 Gb
Ex II 2D Ex tb IIIC T95 °C Db
PSB:
Ex II 2G Ex eb IIC T5, T6 Gb
Ex II 2D Ex tb IIIC T95 °C, T80 °C Db
MSB:
Ex II 2G Ex eb IIC 150 °C (T3), T4 Gb
Ex II 2D Ex tb IIIC T150 °C, T130 °C Db
HSB:
Ex II 2G Ex eb IIC 180 °C (T3), T4 Gb
Ex II 2D Ex tb IIIC T180 °C, T130 °C DbCertification BVS 13 ATEX E 040
IECEx BVS 13.0048X
TC RU C-DE.GB06.B.00230 - Download