Self-limiting parallel heating tape MSB
Product Description | Self-limiting parallel heating tape MSB |
Product Type | 07-5804-2..Y |
Brand | Bartec |
- Self-limiting
- Can be used in temperature class T4 in Ex area
- Can be cut to length at random thanks to its parallel circuit configuration
- Simple installation thanks to its high flexibility and favourable dimensions
- Corrosion-proof and resistant to chemical attack thanks to its protective TPC outer jacket
- Simple installation thanks to its high flexibility and small dimensions
Description
A temperature-dependant resistive element between two parallel copper conductors regulates and limits the heat output of the heating tape. This output regulation is carried out automatically along the entire length of the heating tape according to the prevailing ambient temperature. If the ambient temperature rises, the power output of the tape is reduced.
Thanks to the parallel design the heating tape can be cut to any required length. This feature considerably simplifies project planning and installation. The heating tape is cut and terminated directly on the construction site according to the circumstances. If the tape will be damaged, it is not necessary to replace the whole tape.
Technical Data
Dimensions | with protective braid and protective outer jacket of TPC: 10.2 mm x 4.8 mm Min. bending radius: 25 mm |
Length of heating circuit | see data sheet |
Heat output | at AC 230 V (+10°C): 10 W/m, 15 W/m, 25 W/m, 30 W/m, 40 W/m |
Voltage | Nominal voltage: AC 208 V up to 254 V |
Resistance | Protective braid: < 18.2 Ω/km (< 10.6 Ω/km) |
Ambient temperature | Max. exposure temperature switched on: +110 °C switched off :+130 °C Min. installation temperature: -40 °C Min. start-up temperature: -50 °C |
Explosion Protection
Marking | Ex II 2G Ex e IIC 150 °C (T3), T4 Gb Ex II 2D Ex tb IIIC T 150 °C, T 130 °C Db |
Certification | DEKRA 7ATEX0007U IECEx DEK 17.0004U |
- General Info
-
Description
A temperature-dependant resistive element between two parallel copper conductors regulates and limits the heat output of the heating tape. This output regulation is carried out automatically along the entire length of the heating tape according to the prevailing ambient temperature. If the ambient temperature rises, the power output of the tape is reduced.
Thanks to the parallel design the heating tape can be cut to any required length. This feature considerably simplifies project planning and installation. The heating tape is cut and terminated directly on the construction site according to the circumstances. If the tape will be damaged, it is not necessary to replace the whole tape. - Technical Data
-
Technical Data
Dimensions with protective braid and protective outer
jacket of TPC: 10.2 mm x 4.8 mm
Min. bending radius: 25 mmLength of heating circuit see data sheet Heat output at AC 230 V (+10°C):
10 W/m, 15 W/m, 25 W/m, 30 W/m, 40 W/mVoltage Nominal voltage: AC 208 V up to 254 V Resistance Protective braid: < 18.2 Ω/km (< 10.6 Ω/km) Ambient temperature Max. exposure temperature
switched on: +110 °C
switched off :+130 °C
Min. installation temperature: -40 °C
Min. start-up temperature: -50 °C - Explosion Protection
-
Explosion Protection
Marking Ex II 2G Ex e IIC 150 °C (T3), T4 Gb
Ex II 2D Ex tb IIIC T 150 °C, T 130 °C DbCertification DEKRA 7ATEX0007U