Connection Cable CC 15

Product Description Connection Cable
Product Type CC 15
Brand Listec GmbH
  • Fire alarm cable, type JE-H((St)H…Bd FE180 E30-E90
  • Halogen-free, with improved fire characteristics
  • Applicable up to a maximum operating voltage of 225 V AC
  • The System circuit integrity requirement E30-E90*, according to DIN 4102-12, allows for an operating voltage of up to 110 V AC
  • Temperature range from -30 °C … +70 °C (permanent installation) / -5 °C … +50 °C (during installation)
  • Cable diameter 5,5 mm
  • Two core with additional drain wire
  • May be combined with sensor cable SEC 15 via connection boxes CBO 5 and CBO 15
Datasheet
General Info
  • Fire alarm cable, type JE-H((St)H…Bd FE180 E30-E90
  • Halogen-free, with improved fire characteristics
  • Applicable up to a maximum operating voltage of 225 V AC
  • The System circuit integrity requirement E30-E90*, according to DIN 4102-12, allows for an operating voltage of up to 110 V AC
  • Temperature range from -30 °C … +70 °C (permanent installation) / -5 °C … +50 °C (during installation)
  • Cable diameter 5,5 mm
  • Two core with additional drain wire
  • May be combined with sensor cable SEC 15 via connection boxes CBO 5 and CBO 15
Download
Datasheet